NYC Cooling Tower System Inspection Results

This dataset includes cooling tower regulatory inspection results from the NYC Health Department’s Office of Building Water Systems Oversight (BWSO).

The dataset includes results from two inspection types: cycle or non-cycle. Cycle inspections are regular compliance inspections conducted by BWSO to confirm adherence with cooling tower regulations. Non-cycle may include follow-up inspections or other regulatory inspections to evaluate public health risks.Cooling tower systems that are compliant at the time of inspection have the inspection date with blank values for the violation and citation columns. Building owners that are subject to financial penalties for a cited violation receive a notice of violation with a summons number, as shown in the dataset. The Office of Administrative Trial and Hearings (OATH) adjudicates the summons.

Hearing status and adjudication result are shown separately in the Cooling Tower Hearings dataset (a subset of the OATH Hearings Division Case Status dataset). The summons number in this dataset corresponds with the ticket number field in the Cooling Towers Hearings dataset.

Health Department of Health and Mental Hygiene Dataset f9wb-g8mb 22 fields
DOWNLOAD CSV
Dataset fields
Showing 50 real records
0881222376
Bin: 1089381 • System Id: 2000001843 • Address: 101 AVENUE D
Bin
1089381
System Id
2000001843
Address
101 AVENUE D
Borough
Manhattan
Zip Code
10009
Status
Active
Active Equip
1
Inspection Date
2020-09-28T00:00:00.000
Violation Code
AH8X
Law Section
24 RCNY §8-06(b)(2)
Violation Text
Legionella samples not collected, analyzed before system start-up
Violation Type
General
Citation Text
At the time of inspection, operational records provided by Respondent failed to produce sufficient evidence in the form of a lab report or chain-of-custody form that the required startup-up Legionella culture collection had been conducted during the following documented startup time period: 3-7 days after 6/17/2020
Summons Number
0881222376
Inspection Type
Cycle
Bbl
1003777503
Latitude
40.723506
Longitude
-73.976579
Community Board
103
Council District
2
Census Tract
002602
Nta Code
MN0303
VIEW LOCATION
3259561
Bin: 3259561 • System Id: 2000001847 • Address: 536 MYRTLE AVENUE
Bin
3259561
System Id
2000001847
Address
536 MYRTLE AVENUE
Borough
Brooklyn
Zip Code
11205
Status
Active
Active Equip
1
Inspection Date
2023-07-07T00:00:00.000
Inspection Type
Cycle
Bbl
3019057501
Latitude
40.693456
Longitude
-73.963546
Community Board
302
Council District
35
Census Tract
019300
Nta Code
BK0204
VIEW LOCATION
0881289310
Bin: 3259561 • System Id: 2000001847 • Address: 536 MYRTLE AVENUE
Bin
3259561
System Id
2000001847
Address
536 MYRTLE AVENUE
Borough
Brooklyn
Zip Code
11205
Status
Active
Active Equip
1
Inspection Date
2023-03-20T00:00:00.000
Violation Code
AH8C
Law Section
24 RCNY §8-04(a)
Violation Text
Routine monitoring not conducted, documented at least once a week when tower is in use
Violation Type
Critical
Citation Text
Respondent failed to provide records of all required weekly routine system monitoring. Records were missing for the following week(s) of December 04, 2022 to March 18, 2023, while the cooling tower system was in operation. Operator was unable to provide manual or electronic records during and at the end of completion of the cooling tower inspection.
Summons Number
0881289310
Inspection Type
Cycle
Bbl
3019057501
Latitude
40.693456
Longitude
-73.963546
Community Board
302
Council District
35
Census Tract
019300
Nta Code
BK0204
VIEW LOCATION
0881289320
Bin: 3259561 • System Id: 2000001847 • Address: 536 MYRTLE AVENUE
Bin
3259561
System Id
2000001847
Address
536 MYRTLE AVENUE
Borough
Brooklyn
Zip Code
11205
Status
Active
Active Equip
1
Inspection Date
2023-03-20T00:00:00.000
Violation Code
AH8D
Law Section
24 RCNY §8-04(b)
Violation Text
Compliance inspections not conducted, documented at least once every 90 days when the tower is in use
Violation Type
Critical
Citation Text
Compliance inspections must be completed by a Qualified Person every 90 days while the cooling tower system is in operation. Respondent failed to provide documentation of compliance inspection for the 90 day period due by March 01, 2023. Last DOH inspection was conducted on December 01, 2022. Operator was unable to provide manual or electronic records during and at the end of completion of the cooling tower inspection.
Summons Number
0881289320
Inspection Type
Cycle
Bbl
3019057501
Latitude
40.693456
Longitude
-73.963546
Community Board
302
Council District
35
Census Tract
019300
Nta Code
BK0204
VIEW LOCATION
3259561
Bin: 3259561 • System Id: 2000001847 • Address: 536 MYRTLE AVENUE
Bin
3259561
System Id
2000001847
Address
536 MYRTLE AVENUE
Borough
Brooklyn
Zip Code
11205
Status
Active
Active Equip
1
Inspection Date
2023-03-20T00:00:00.000
Violation Code
AH8E
Law Section
24 RCNY §8-04(c)
Violation Text
Routine maintenance according to Maintenance Program and Plan not conducted or documented
Violation Type
General
Citation Text
Respondent failed to demonstrate proof that all routine maintenance was conducted or documented while the cooling tower system was in operation. Records were missing the following date(s): pertinent records not provided
Inspection Type
Cycle
Bbl
3019057501
Latitude
40.693456
Longitude
-73.963546
Community Board
302
Council District
35
Census Tract
019300
Nta Code
BK0204
VIEW LOCATION
0881289339
Bin: 3259561 • System Id: 2000001847 • Address: 536 MYRTLE AVENUE
Bin
3259561
System Id
2000001847
Address
536 MYRTLE AVENUE
Borough
Brooklyn
Zip Code
11205
Status
Active
Active Equip
1
Inspection Date
2023-03-20T00:00:00.000
Violation Code
AH8F
Law Section
24 RCNY §8-04(d)
Violation Text
Twice yearly or other required cleaning not conducted or documented
Violation Type
Critical
Citation Text
At the time of inspection, Respondent failed to provide records demonstrating that cooling tower cleaning was conducted at all within the previous year (2022) of operation. Last DOH inspection was conducted on December 01, 2022. Operator was unable to provide manual or electronic records during and at the end of completion of the cooling tower inspection.
Summons Number
0881289339
Inspection Type
Cycle
Bbl
3019057501
Latitude
40.693456
Longitude
-73.963546
Community Board
302
Council District
35
Census Tract
019300
Nta Code
BK0204
VIEW LOCATION
0881289348
Bin: 3259561 • System Id: 2000001847 • Address: 536 MYRTLE AVENUE
Bin
3259561
System Id
2000001847
Address
536 MYRTLE AVENUE
Borough
Brooklyn
Zip Code
11205
Status
Active
Active Equip
1
Inspection Date
2023-03-20T00:00:00.000
Violation Code
AH8L
Law Section
24 RCNY §8-05(c)(3)
Violation Text
No records of all chemicals and biocides (C&B) added
Violation Type
Critical
Citation Text
Respondent failed to provide chemical and biocide usage records for chemicals used on-site, while cooling tower was in operation. During the inspection, Inspector observed the following chemicals being used on site: Kathon 25 BF, Stabrom 909 Biocide and WES CT-902C. Operator was unable to provide manual or electronic records during and at the end of completion of the cooling tower inspection.
Summons Number
0881289348
Inspection Type
Cycle
Bbl
3019057501
Latitude
40.693456
Longitude
-73.963546
Community Board
302
Council District
35
Census Tract
019300
Nta Code
BK0204
VIEW LOCATION
0881289357
Bin: 3259561 • System Id: 2000001847 • Address: 536 MYRTLE AVENUE
Bin
3259561
System Id
2000001847
Address
536 MYRTLE AVENUE
Borough
Brooklyn
Zip Code
11205
Status
Active
Active Equip
1
Inspection Date
2023-03-20T00:00:00.000
Violation Code
AH8Q
Law Section
24 RCNY §8-05(f)(1)
Violation Text
Minimum daily water quality measurements not taken or recorded (or if automated, not viewable)
Violation Type
General
Citation Text
Measurements of water quality parameter must occur at least 3 times each week while the cooling tower system is operating. Respondent failed to provide records of manual and/or required automatic collection of water quality parameters taken from December 04, 2022 to March 18, 2023, while the cooling tower system was in operation. Operator was unable to provide manual or electronic records during and at the end of completion of the cooling tower inspection.
Summons Number
0881289357
Inspection Type
Cycle
Bbl
3019057501
Latitude
40.693456
Longitude
-73.963546
Community Board
302
Council District
35
Census Tract
019300
Nta Code
BK0204
VIEW LOCATION
0881289366
Bin: 3259561 • System Id: 2000001847 • Address: 536 MYRTLE AVENUE
Bin
3259561
System Id
2000001847
Address
536 MYRTLE AVENUE
Borough
Brooklyn
Zip Code
11205
Status
Active
Active Equip
1
Inspection Date
2023-03-20T00:00:00.000
Violation Code
AH8R
Law Section
24 RCNY §8-05(f)(2)
Violation Text
Failure to collect, analyze or record weekly biological process control indicators
Violation Type
Critical
Citation Text
Respondent failed to produce records demonstrating that the required weekly collection of bacteriological indicators of re-circulating water was conducted since the Department's previous cycle inspection of December 01, 2022. On-site representative was requested to provide missing records taken from December 04, 2022 to March 18, 2023, while the cooling tower system was in operation. Operator was unable to provide manual or electronic records during inspection and at final review of violation deficiencies but was not able to do so.
Summons Number
0881289366
Inspection Type
Cycle
Bbl
3019057501
Latitude
40.693456
Longitude
-73.963546
Community Board
302
Council District
35
Census Tract
019300
Nta Code
BK0204
VIEW LOCATION
0881289375
Bin: 3259561 • System Id: 2000001847 • Address: 536 MYRTLE AVENUE
Bin
3259561
System Id
2000001847
Address
536 MYRTLE AVENUE
Borough
Brooklyn
Zip Code
11205
Status
Active
Active Equip
1
Inspection Date
2023-03-20T00:00:00.000
Violation Code
AH8S
Law Section
24 RCNY §8-05(f)(3)
Violation Text
Legionella samples not collected or analyzed, or results not recorded or reported to DOHMH as required
Violation Type
PHH
Citation Text
At the time of inspection, Respondent failed to demonstrate by either lab report or chain of custody form that all required Legionella samples were taken while the cooling tower system was in operation. Last DOH inspection was conducted on December 01, 2022. On-site representative was requested to provide missing record due by March 01, 2023, while the cooling tower system was in operation. Operator was unable to provide manual or electronic records during inspection and at final review of violation deficiencies but was not able to do so.
Summons Number
0881289375
Inspection Type
Cycle
Bbl
3019057501
Latitude
40.693456
Longitude
-73.963546
Community Board
302
Council District
35
Census Tract
019300
Nta Code
BK0204
VIEW LOCATION
0881289384
Bin: 3259561 • System Id: 2000001847 • Address: 536 MYRTLE AVENUE
Bin
3259561
System Id
2000001847
Address
536 MYRTLE AVENUE
Borough
Brooklyn
Zip Code
11205
Status
Active
Active Equip
1
Inspection Date
2023-03-20T00:00:00.000
Violation Code
AH8T
Law Section
24 RCNY §8-05(f)(4)
Violation Text
Failure to monitor and sample from representative locations and times
Violation Type
Critical
Citation Text
At the time of inspection, Respondent failed to produce records demonstrating proof of water quality monitoring sample times and sampling locations, failed to produce records of required locations and sample times for bacteriological indicator samples not collected on the following dates of December 04, 2022 to March 18, 2023, and failed to provide records of sample times and locations of Legionella sampling due by March 1, 2023 respectively. Operator was unable to provide manual or electronic records during inspection and at final review of violation deficiencies but was not able to do so.
Summons Number
0881289384
Inspection Type
Cycle
Bbl
3019057501
Latitude
40.693456
Longitude
-73.963546
Community Board
302
Council District
35
Census Tract
019300
Nta Code
BK0204
VIEW LOCATION
0881289393
Bin: 3259561 • System Id: 2000001847 • Address: 536 MYRTLE AVENUE
Bin
3259561
System Id
2000001847
Address
536 MYRTLE AVENUE
Borough
Brooklyn
Zip Code
11205
Status
Active
Active Equip
1
Inspection Date
2023-03-20T00:00:00.000
Violation Code
AH8X
Law Section
24 RCNY §8-06(b)(2)
Violation Text
Legionella samples not collected, analyzed before system start-up
Violation Type
General
Citation Text
At the time of inspection, Respondent failed to produce sufficient evidence in the form of a lab report or chain-of-custody form that the required startup Legionella culture test had been completed during the documented startup time period. Operator was unable to provide any records demonstrating that the tower is not used seasonally when requested on site.
Summons Number
0881289393
Inspection Type
Cycle
Bbl
3019057501
Latitude
40.693456
Longitude
-73.963546
Community Board
302
Council District
35
Census Tract
019300
Nta Code
BK0204
VIEW LOCATION
0196823927
Bin: 3259561 • System Id: 2000001847 • Address: 536 MYRTLE AVENUE
Bin
3259561
System Id
2000001847
Address
536 MYRTLE AVENUE
Borough
Brooklyn
Zip Code
11205
Status
Active
Active Equip
1
Inspection Date
2023-02-16T00:00:00.000
Violation Code
AH8U
Law Section
24 RCNY §8-05(f)(5)
Violation Text
Required corrective actions not taken based on bacteriological results
Violation Type
PHH
Summons Number
0196823927
Inspection Type
Non-Cycle
Bbl
3019057501
Latitude
40.693456
Longitude
-73.963546
Community Board
302
Council District
35
Census Tract
019300
Nta Code
BK0204
VIEW LOCATION
1037574
Bin: 1037574 • System Id: 2000000783 • Address: 279 EAST 44TH STREET
Bin
1037574
System Id
2000000783
Address
279 EAST 44TH STREET
Borough
Manhattan
Zip Code
10017
Status
Active
Active Equip
1
Inspection Date
2024-05-03T00:00:00.000
Inspection Type
Cycle
Bbl
1013180022
Latitude
40.751523
Longitude
-73.971382
Community Board
106
Council District
4
Census Tract
009000
Nta Code
MN0604
VIEW LOCATION
0881282445
Bin: 3259561 • System Id: 2000001847 • Address: 536 MYRTLE AVENUE
Bin
3259561
System Id
2000001847
Address
536 MYRTLE AVENUE
Borough
Brooklyn
Zip Code
11205
Status
Active
Active Equip
1
Inspection Date
2022-12-01T00:00:00.000
Violation Code
AH8A
Law Section
24 RCNY §8-03
Violation Text
No Maintenance Program or Plan
Violation Type
PHH
Citation Text
Respondent's required Maintenance Program and Plan for the registered cooling tower system identified above was not produced to the Department upon request on the date and time of inspection noted above. The on-site representative was requested to provide missing record during inspection and at final review of violation deficiencies but was not able to do so.
Summons Number
0881282445
Inspection Type
Cycle
Bbl
3019057501
Latitude
40.693456
Longitude
-73.963546
Community Board
302
Council District
35
Census Tract
019300
Nta Code
BK0204
VIEW LOCATION
0881282454
Bin: 3259561 • System Id: 2000001847 • Address: 536 MYRTLE AVENUE
Bin
3259561
System Id
2000001847
Address
536 MYRTLE AVENUE
Borough
Brooklyn
Zip Code
11205
Status
Active
Active Equip
1
Inspection Date
2022-12-01T00:00:00.000
Violation Code
AH8C
Law Section
24 RCNY §8-04(a)
Violation Text
Routine monitoring not conducted, documented at least once a week when tower is in use
Violation Type
Critical
Citation Text
Respondent failed to provide records of all required weekly routine system monitoring. Records were missing for the following time period while the cooling tower system was in operation: 5/20/2021 - 12/01/2022
Summons Number
0881282454
Inspection Type
Cycle
Bbl
3019057501
Latitude
40.693456
Longitude
-73.963546
Community Board
302
Council District
35
Census Tract
019300
Nta Code
BK0204
VIEW LOCATION
0881282463
Bin: 3259561 • System Id: 2000001847 • Address: 536 MYRTLE AVENUE
Bin
3259561
System Id
2000001847
Address
536 MYRTLE AVENUE
Borough
Brooklyn
Zip Code
11205
Status
Active
Active Equip
1
Inspection Date
2022-12-01T00:00:00.000
Violation Code
AH8D
Law Section
24 RCNY §8-04(b)
Violation Text
Compliance inspections not conducted, documented at least once every 90 days when the tower is in use
Violation Type
Critical
Citation Text
Compliance inspections must be completed by a Qualified Person every 90 days while the cooling tower system is in operation. Respondent failed to provide documentation of compliance inspections conducted every 90 days for the following time period while the cooling tower system was in operation: 5/20/2021 - 12/01/2022
Summons Number
0881282463
Inspection Type
Cycle
Bbl
3019057501
Latitude
40.693456
Longitude
-73.963546
Community Board
302
Council District
35
Census Tract
019300
Nta Code
BK0204
VIEW LOCATION
3259561
Bin: 3259561 • System Id: 2000001847 • Address: 536 MYRTLE AVENUE
Bin
3259561
System Id
2000001847
Address
536 MYRTLE AVENUE
Borough
Brooklyn
Zip Code
11205
Status
Active
Active Equip
1
Inspection Date
2022-12-01T00:00:00.000
Violation Code
AH8E
Law Section
24 RCNY §8-04(c)
Violation Text
Routine maintenance according to Maintenance Program and Plan not conducted or documented
Violation Type
General
Citation Text
Respondent failed to demonstrate proof that all routine maintenance was conducted or documented while the cooling tower system was in operation. Records were missing the following date(s): pertinent records not provided
Inspection Type
Cycle
Bbl
3019057501
Latitude
40.693456
Longitude
-73.963546
Community Board
302
Council District
35
Census Tract
019300
Nta Code
BK0204
VIEW LOCATION
0881282472
Bin: 3259561 • System Id: 2000001847 • Address: 536 MYRTLE AVENUE
Bin
3259561
System Id
2000001847
Address
536 MYRTLE AVENUE
Borough
Brooklyn
Zip Code
11205
Status
Active
Active Equip
1
Inspection Date
2022-12-01T00:00:00.000
Violation Code
AH8F
Law Section
24 RCNY §8-04(d)
Violation Text
Twice yearly or other required cleaning not conducted or documented
Violation Type
Critical
Citation Text
At the time of inspection, Respondent failed to provide records demonstrating that cooling tower cleaning was conducted at all within the previous year of operation.
Summons Number
0881282472
Inspection Type
Cycle
Bbl
3019057501
Latitude
40.693456
Longitude
-73.963546
Community Board
302
Council District
35
Census Tract
019300
Nta Code
BK0204
VIEW LOCATION
0881282481
Bin: 3259561 • System Id: 2000001847 • Address: 536 MYRTLE AVENUE
Bin
3259561
System Id
2000001847
Address
536 MYRTLE AVENUE
Borough
Brooklyn
Zip Code
11205
Status
Active
Active Equip
1
Inspection Date
2022-12-01T00:00:00.000
Violation Code
AH8H
Law Section
24 RCNY §8-05(a)
Violation Text
Daily automatic or approved alternative water treatment plan not provided
Violation Type
Critical
Citation Text
At the time of inspection, upon Inspector's review of records provided by on-site representative and physical observation of the operating cooling tower system, the Respondent failed to provide required proof of daily automated treatment or alternative approved chemical water treatment plan. At the time of inspection, upon review of operational records provided by on-site representative and Inspector's physical observation of the operating cooling tower system, Respondent failed to provide proof of either documentation of chemical treatment during cooling tower system operation, or a DOHMH approved alternative water treatment plan that justified the absence of chemical treatment.
Summons Number
0881282481
Inspection Type
Cycle
Bbl
3019057501
Latitude
40.693456
Longitude
-73.963546
Community Board
302
Council District
35
Census Tract
019300
Nta Code
BK0204
VIEW LOCATION
0881282490
Bin: 3259561 • System Id: 2000001847 • Address: 536 MYRTLE AVENUE
Bin
3259561
System Id
2000001847
Address
536 MYRTLE AVENUE
Borough
Brooklyn
Zip Code
11205
Status
Active
Active Equip
1
Inspection Date
2022-12-01T00:00:00.000
Violation Code
AH8K
Law Section
24 RCNY §8-05(c)(2)
Violation Text
Use of an unregistered biocide product
Violation Type
General
Citation Text
Respondent failed to provide the New York State Department of Environmental Conservation (NYS DEC) approved registration stamp or PIMS application demonstrating proof of NYS DEC biocide registration.
Summons Number
0881282490
Inspection Type
Cycle
Bbl
3019057501
Latitude
40.693456
Longitude
-73.963546
Community Board
302
Council District
35
Census Tract
019300
Nta Code
BK0204
VIEW LOCATION
0881282500
Bin: 3259561 • System Id: 2000001847 • Address: 536 MYRTLE AVENUE
Bin
3259561
System Id
2000001847
Address
536 MYRTLE AVENUE
Borough
Brooklyn
Zip Code
11205
Status
Active
Active Equip
1
Inspection Date
2022-12-01T00:00:00.000
Violation Code
AH8L
Law Section
24 RCNY §8-05(c)(3)
Violation Text
No records of all chemicals and biocides (C&B) added
Violation Type
Critical
Citation Text
Respondent failed to provide chemical and biocide usage records or safety data sheets (SDS) noting manufacturer's name, brand and purpose for chemicals used on-site.
Summons Number
0881282500
Inspection Type
Cycle
Bbl
3019057501
Latitude
40.693456
Longitude
-73.963546
Community Board
302
Council District
35
Census Tract
019300
Nta Code
BK0204
VIEW LOCATION
3259561
Bin: 3259561 • System Id: 2000001847 • Address: 536 MYRTLE AVENUE
Bin
3259561
System Id
2000001847
Address
536 MYRTLE AVENUE
Borough
Brooklyn
Zip Code
11205
Status
Active
Active Equip
1
Inspection Date
2022-12-01T00:00:00.000
Violation Code
AH8Q
Law Section
24 RCNY §8-05(f)(1)
Violation Text
Minimum daily water quality measurements not taken or recorded (or if automated, not viewable)
Violation Type
General
Citation Text
Measurements of water quality parameter must occur at least 3 times each week while the cooling tower system is operating. Respondent failed to provide records of manual collection of water quality parameters while the cooling tower system was in operation. Respondent failed to provide records of required automatic collection of water quality parameters for the previous year of cooling tower operation.
Inspection Type
Cycle
Bbl
3019057501
Latitude
40.693456
Longitude
-73.963546
Community Board
302
Council District
35
Census Tract
019300
Nta Code
BK0204
VIEW LOCATION
0881249820
Bin: 4210455 • System Id: 2000012582 • Address: 87-50 167TH STREET
Bin
4210455
System Id
2000012582
Address
87-50 167TH STREET
Borough
Queens
Zip Code
11432
Status
Inactive
Active Equip
0
Inspection Date
2021-05-14T00:00:00.000
Violation Code
AH8A
Law Section
24 RCNY §8-03
Violation Text
No Maintenance Program or Plan
Violation Type
PHH
Citation Text
Respondent is in violation of 24 RCNY 8-03 in that an MPP for the registered cooling tower system identified above was not produced to the Department upon request on the date and time of inspection noted above. The on-site representative did not provide an MPP
Summons Number
0881249820
Inspection Type
Cycle
Bbl
4098380062
Latitude
40.710054
Longitude
-73.796277
Community Board
408
Council District
24
Census Tract
045400
Nta Code
QN0805
VIEW LOCATION
0881282519
Bin: 3259561 • System Id: 2000001847 • Address: 536 MYRTLE AVENUE
Bin
3259561
System Id
2000001847
Address
536 MYRTLE AVENUE
Borough
Brooklyn
Zip Code
11205
Status
Active
Active Equip
1
Inspection Date
2022-12-01T00:00:00.000
Violation Code
AH8R
Law Section
24 RCNY §8-05(f)(2)
Violation Text
Failure to collect, analyze or record weekly biological process control indicators
Violation Type
Critical
Citation Text
Respondent failed to produce records demonstrating that the required weekly collection of bacteriological indicators of re-circulating water was conducted since the Department's previous cycle inspection. On-site representative was requested to provide missing records during inspection and at final review of violation deficiencies but was not able to do so.
Summons Number
0881282519
Inspection Type
Cycle
Bbl
3019057501
Latitude
40.693456
Longitude
-73.963546
Community Board
302
Council District
35
Census Tract
019300
Nta Code
BK0204
VIEW LOCATION
0881282528
Bin: 3259561 • System Id: 2000001847 • Address: 536 MYRTLE AVENUE
Bin
3259561
System Id
2000001847
Address
536 MYRTLE AVENUE
Borough
Brooklyn
Zip Code
11205
Status
Active
Active Equip
1
Inspection Date
2022-12-01T00:00:00.000
Violation Code
AH8S
Law Section
24 RCNY §8-05(f)(3)
Violation Text
Legionella samples not collected or analyzed, or results not recorded or reported to DOHMH as required
Violation Type
PHH
Citation Text
At the time of inspection, Respondent failed to demonstrate by either lab report or chain of custody form that all required Legionella samples were taken for the following time period while the cooling tower system was in operation: 5/20/2021 - 12/01/2022
Summons Number
0881282528
Inspection Type
Cycle
Bbl
3019057501
Latitude
40.693456
Longitude
-73.963546
Community Board
302
Council District
35
Census Tract
019300
Nta Code
BK0204
VIEW LOCATION
0881282537
Bin: 3259561 • System Id: 2000001847 • Address: 536 MYRTLE AVENUE
Bin
3259561
System Id
2000001847
Address
536 MYRTLE AVENUE
Borough
Brooklyn
Zip Code
11205
Status
Active
Active Equip
1
Inspection Date
2022-12-01T00:00:00.000
Violation Code
AH8T
Law Section
24 RCNY §8-05(f)(4)
Violation Text
Failure to monitor and sample from representative locations and times
Violation Type
Critical
Citation Text
At the time of inspection, Respondent failed to produce records demonstrating proof of water quality monitoring, bacteriological indicator sampling, and Legionella sampling being collected at a time and a location representative of the water circulating in the Cooling Tower System.
Summons Number
0881282537
Inspection Type
Cycle
Bbl
3019057501
Latitude
40.693456
Longitude
-73.963546
Community Board
302
Council District
35
Census Tract
019300
Nta Code
BK0204
VIEW LOCATION
0881282546
Bin: 3259561 • System Id: 2000001847 • Address: 536 MYRTLE AVENUE
Bin
3259561
System Id
2000001847
Address
536 MYRTLE AVENUE
Borough
Brooklyn
Zip Code
11205
Status
Active
Active Equip
1
Inspection Date
2022-12-01T00:00:00.000
Violation Code
AH8X
Law Section
24 RCNY §8-06(b)(2)
Violation Text
Legionella samples not collected, analyzed before system start-up
Violation Type
General
Citation Text
At the time of inspection, Respondent failed to produce sufficient evidence in the form of a lab report or chain-of-custody form that the required startup Legionella culture test had been completed during the undocumented startup time period.
Summons Number
0881282546
Inspection Type
Cycle
Bbl
3019057501
Latitude
40.693456
Longitude
-73.963546
Community Board
302
Council District
35
Census Tract
019300
Nta Code
BK0204
VIEW LOCATION
3259561
Bin: 3259561 • System Id: 2000001847 • Address: 536 MYRTLE AVENUE
Bin
3259561
System Id
2000001847
Address
536 MYRTLE AVENUE
Borough
Brooklyn
Zip Code
11205
Status
Active
Active Equip
1
Inspection Date
2022-12-01T00:00:00.000
Violation Code
AH9C
Law Section
24 RCNY §8-07(c)
Violation Text
DOB Cooling Tower Registration Number not posted as required
Violation Type
General
Citation Text
Respondent is in violation of 8-07(c) in that, at the time of inspection, Inspector observed that the cooling tower system's Department of Buildings Cooling Tower registration number was not posted on the cooling tower.
Inspection Type
Cycle
Bbl
3019057501
Latitude
40.693456
Longitude
-73.963546
Community Board
302
Council District
35
Census Tract
019300
Nta Code
BK0204
VIEW LOCATION
0196804740
Bin: 3259561 • System Id: 2000001847 • Address: 536 MYRTLE AVENUE
Bin
3259561
System Id
2000001847
Address
536 MYRTLE AVENUE
Borough
Brooklyn
Zip Code
11205
Status
Active
Active Equip
1
Inspection Date
2022-01-11T00:00:00.000
Violation Code
AH8U
Law Section
24 RCNY §8-05(f)(5)
Violation Text
Required corrective actions not taken based on bacteriological results
Violation Type
PHH
Summons Number
0196804740
Inspection Type
Non-Cycle
Bbl
3019057501
Latitude
40.693456
Longitude
-73.963546
Community Board
302
Council District
35
Census Tract
019300
Nta Code
BK0204
VIEW LOCATION
0881245732
Bin: 3259561 • System Id: 2000001847 • Address: 536 MYRTLE AVENUE
Bin
3259561
System Id
2000001847
Address
536 MYRTLE AVENUE
Borough
Brooklyn
Zip Code
11205
Status
Active
Active Equip
1
Inspection Date
2021-05-19T00:00:00.000
Violation Code
AH8A
Law Section
24 RCNY §8-03
Violation Text
No Maintenance Program or Plan
Violation Type
PHH
Citation Text
Respondent is in violation of 24 RCNY 8-03 in that an MPP for the registered cooling tower system identified above was not produced to the Department upon request on the date and time of inspection noted above. The on-site representative was requested to provide missing record during inspection and at final review of violation deficiencies but was not able to do so. The manager on site Mr. Charlie stated he has no calender year 2020-2021 maintenance program plan for said cooling tower on the premise at time of inspection.
Summons Number
0881245732
Inspection Type
Cycle
Bbl
3019057501
Latitude
40.693456
Longitude
-73.963546
Community Board
302
Council District
35
Census Tract
019300
Nta Code
BK0204
VIEW LOCATION
0881245741
Bin: 3259561 • System Id: 2000001847 • Address: 536 MYRTLE AVENUE
Bin
3259561
System Id
2000001847
Address
536 MYRTLE AVENUE
Borough
Brooklyn
Zip Code
11205
Status
Active
Active Equip
1
Inspection Date
2021-05-19T00:00:00.000
Violation Code
AH8C
Law Section
24 RCNY §8-04(a)
Violation Text
Routine monitoring not conducted, documented at least once a week when tower is in use
Violation Type
Critical
Citation Text
Respondent is in violation of 24 RCNY 8-04(a)(1) in that the operational records provided by on-site representative and reviewed by Department at the time of inspection failed to demonstrate that all weekly routine system monitoring had taken place while the cooling tower system was in operation.On site person Mr Charlie informed inspectors that location has no calender year 2020-2021 operational records at time of inspection.
Summons Number
0881245741
Inspection Type
Cycle
Bbl
3019057501
Latitude
40.693456
Longitude
-73.963546
Community Board
302
Council District
35
Census Tract
019300
Nta Code
BK0204
VIEW LOCATION
0881245750
Bin: 3259561 • System Id: 2000001847 • Address: 536 MYRTLE AVENUE
Bin
3259561
System Id
2000001847
Address
536 MYRTLE AVENUE
Borough
Brooklyn
Zip Code
11205
Status
Active
Active Equip
1
Inspection Date
2021-05-19T00:00:00.000
Violation Code
AH8D
Law Section
24 RCNY §8-04(b)
Violation Text
Compliance inspections not conducted, documented at least once every 90 days when the tower is in use
Violation Type
Critical
Citation Text
Compliance inspections must be completed by a Qualified Person every 90 days while the cooling tower system is in operation. Respondent is in violation of 24 RCNY 8-04(b) in that records provided by on-site representative and reviewed by Department at the time of inspection failed to provide documentation of compliance inspection for the following date(s): pertinent records not provided. On site person Mr. Charlie informed inspectors that location has no calender year 2020-2021 operational records at time of inspection.
Summons Number
0881245750
Inspection Type
Cycle
Bbl
3019057501
Latitude
40.693456
Longitude
-73.963546
Community Board
302
Council District
35
Census Tract
019300
Nta Code
BK0204
VIEW LOCATION
3259561
Bin: 3259561 • System Id: 2000001847 • Address: 536 MYRTLE AVENUE
Bin
3259561
System Id
2000001847
Address
536 MYRTLE AVENUE
Borough
Brooklyn
Zip Code
11205
Status
Active
Active Equip
1
Inspection Date
2021-05-19T00:00:00.000
Violation Code
AH8E
Law Section
24 RCNY §8-04(c)
Violation Text
Routine maintenance according to Maintenance Program and Plan not conducted or documented
Violation Type
General
Citation Text
At the time of inspection, operational records provided by on-site representative and reviewed by Department failed to demonstrate proof that routine maintenance was conducted or documented for the following date(s) while the cooling tower system was in operation: pertinent records not provided
Inspection Type
Cycle
Bbl
3019057501
Latitude
40.693456
Longitude
-73.963546
Community Board
302
Council District
35
Census Tract
019300
Nta Code
BK0204
VIEW LOCATION
0881245760
Bin: 3259561 • System Id: 2000001847 • Address: 536 MYRTLE AVENUE
Bin
3259561
System Id
2000001847
Address
536 MYRTLE AVENUE
Borough
Brooklyn
Zip Code
11205
Status
Active
Active Equip
1
Inspection Date
2021-05-19T00:00:00.000
Violation Code
AH8F
Law Section
24 RCNY §8-04(d)
Violation Text
Twice yearly or other required cleaning not conducted or documented
Violation Type
Critical
Citation Text
At the time of inspection, operational records provided by on-site representative and reviewed by the Department failed to demonstrate proof that cleaning was conducted at all within the previous year of cooling tower operation. On site person Mr. Charlie informed inspectors that location has no calender year 2020-2021 operational records at time of inspection.
Summons Number
0881245760
Inspection Type
Cycle
Bbl
3019057501
Latitude
40.693456
Longitude
-73.963546
Community Board
302
Council District
35
Census Tract
019300
Nta Code
BK0204
VIEW LOCATION
0881286441
Bin: 3326830 • System Id: 2000012212 • Address: 5100 KINGS PLAZA
Bin
3326830
System Id
2000012212
Address
5100 KINGS PLAZA
Borough
Brooklyn
Zip Code
11234
Status
Active
Active Equip
1
Inspection Date
2023-02-16T00:00:00.000
Violation Code
AH8R
Law Section
24 RCNY §8-05(f)(2)
Violation Text
Failure to collect, analyze or record weekly biological process control indicators
Violation Type
Critical
Citation Text
At the time of inspection,Respondent failed to produce records demonstrating that the required weekly collection of bacteriological indicators of re-circulating water were conducted while the cooling tower system was in operation between the period 10/21/2022 [ last recorded sample ]-02/16/2023 [ current inspection ].Operational records were provided by the Chief Engineer Vincent Baguio.
Summons Number
0881286441
Inspection Type
Cycle
Bbl
3084700055
Latitude
40.60972
Longitude
-73.919516
Community Board
318
Council District
46
Census Tract
069800
Nta Code
BK1802
VIEW LOCATION
0881245779
Bin: 3259561 • System Id: 2000001847 • Address: 536 MYRTLE AVENUE
Bin
3259561
System Id
2000001847
Address
536 MYRTLE AVENUE
Borough
Brooklyn
Zip Code
11205
Status
Active
Active Equip
1
Inspection Date
2021-05-19T00:00:00.000
Violation Code
AH8H
Law Section
24 RCNY §8-05(a)
Violation Text
Daily automatic or approved alternative water treatment plan not provided
Violation Type
Critical
Citation Text
At the time of inspection, upon Inspector's review of records provided by on-site representative and physical observation of the operating cooling tower system, the Respondent failed to provide required proof of daily automated treatment or alternative approved chemical water treatment plan. At the time of inspection, upon review of operational records provided by on-site representative and Inspector's physical observation of the operating cooling tower system, Respondent failed to provide proof of either documentation of chemical treatment during cooling tower system operation, or a DOHMH approved alternative water treatment plan that justified the absence of chemical treatment. The manager on site Mr. Charlie stated he has no calender year 2020-2021 maintenance program plan for said cooling tower on the premise at time of inspection.
Summons Number
0881245779
Inspection Type
Cycle
Bbl
3019057501
Latitude
40.693456
Longitude
-73.963546
Community Board
302
Council District
35
Census Tract
019300
Nta Code
BK0204
VIEW LOCATION
0881245788
Bin: 3259561 • System Id: 2000001847 • Address: 536 MYRTLE AVENUE
Bin
3259561
System Id
2000001847
Address
536 MYRTLE AVENUE
Borough
Brooklyn
Zip Code
11205
Status
Active
Active Equip
1
Inspection Date
2021-05-19T00:00:00.000
Violation Code
AH8K
Law Section
24 RCNY §8-05(c)(2)
Violation Text
Use of an unregistered biocide product
Violation Type
General
Citation Text
At the time of inspection, and upon Inspector's request for records and complete review of the Respondent's cooling tower records as produced by its on-site representative, Respondent failed to provide DEC approved registration stamp or PIMS application demonstrating proof of NYS DEC biocide registration.
Summons Number
0881245788
Inspection Type
Cycle
Bbl
3019057501
Latitude
40.693456
Longitude
-73.963546
Community Board
302
Council District
35
Census Tract
019300
Nta Code
BK0204
VIEW LOCATION
1075741
Bin: 1075741 • System Id: 2000000003 • Address: 109 LAFAYETTE STREET
Bin
1075741
System Id
2000000003
Address
109 LAFAYETTE STREET
Borough
Manhattan
Zip Code
10013
Status
Active
Active Equip
1
Inspection Date
2017-05-26T00:00:00.000
Violation Code
AH8V
Law Section
24 RCNY §8-06(a)
Violation Text
Improper or inadequate shutdown procedures
Violation Type
General
Citation Text
Equipment observed to be inadequately drained and protected.
Inspection Type
Cycle
Bbl
1001977501
Latitude
40.717925
Longitude
-74.000595
Community Board
101
Council District
1
Census Tract
003100
Nta Code
MN0102
VIEW LOCATION
0881245797
Bin: 3259561 • System Id: 2000001847 • Address: 536 MYRTLE AVENUE
Bin
3259561
System Id
2000001847
Address
536 MYRTLE AVENUE
Borough
Brooklyn
Zip Code
11205
Status
Active
Active Equip
1
Inspection Date
2021-05-19T00:00:00.000
Violation Code
AH8L
Law Section
24 RCNY §8-05(c)(3)
Violation Text
No records of all chemicals and biocides (C&B) added
Violation Type
Critical
Citation Text
At the time of inspection, upon Inspector's request for and complete review of records, Respondent failed to provide chemical and biocide usage records or safety data sheets (SDS) noting manufacturer's name, brand and purpose for chemicals used on-site. On site person Mr. Charlie informed inspectors that location has no calender year 2020-2021 operational records at time of inspection.
Summons Number
0881245797
Inspection Type
Cycle
Bbl
3019057501
Latitude
40.693456
Longitude
-73.963546
Community Board
302
Council District
35
Census Tract
019300
Nta Code
BK0204
VIEW LOCATION
3259561
Bin: 3259561 • System Id: 2000001847 • Address: 536 MYRTLE AVENUE
Bin
3259561
System Id
2000001847
Address
536 MYRTLE AVENUE
Borough
Brooklyn
Zip Code
11205
Status
Active
Active Equip
1
Inspection Date
2021-05-19T00:00:00.000
Violation Code
AH8Q
Law Section
24 RCNY §8-05(f)(1)
Violation Text
Minimum daily water quality measurements not taken or recorded (or if automated, not viewable)
Violation Type
General
Citation Text
Manual measurements of water quality parameter must occur at least 3 times each week while the cooling tower system is operating, as per §8-05(f)(1)(A). Operational records produced by on-site representative and reviewed by Department at the time of inspection failed to demonstrate that the manual collection of water quality parameters of re-circulating water was attempted or completed while the cooling tower system was in operation. Operational records produced by on-site representative and reviewed by Department at the time of inspection failed to demonstrate that the required automatic collection of water quality parameters of re-circulating water was conducted for the previous year while the cooling tower system was in operation, as per §8-05(f)(1)(B).
Inspection Type
Cycle
Bbl
3019057501
Latitude
40.693456
Longitude
-73.963546
Community Board
302
Council District
35
Census Tract
019300
Nta Code
BK0204
VIEW LOCATION
0881245806
Bin: 3259561 • System Id: 2000001847 • Address: 536 MYRTLE AVENUE
Bin
3259561
System Id
2000001847
Address
536 MYRTLE AVENUE
Borough
Brooklyn
Zip Code
11205
Status
Active
Active Equip
1
Inspection Date
2021-05-19T00:00:00.000
Violation Code
AH8R
Law Section
24 RCNY §8-05(f)(2)
Violation Text
Failure to collect, analyze or record weekly biological process control indicators
Violation Type
Critical
Citation Text
At the time of inspection, and upon Inspector's request for records and complete review of Respondent's cooling tower records as produced by its on-site representative, Respondent failed to demonstrate that the required weekly collection of bacteriological indicators of re-circulating water was attempted or completed while the cooling tower system was in operation. On-site representative was requested to provide missing records during inspection and at final review of violation deficiencies but was not able to do so. On site person Mr. Charlie informed inspectors that location has no calender year 2020-2021 operational records at time of inspection.
Summons Number
0881245806
Inspection Type
Cycle
Bbl
3019057501
Latitude
40.693456
Longitude
-73.963546
Community Board
302
Council District
35
Census Tract
019300
Nta Code
BK0204
VIEW LOCATION
0881245815
Bin: 3259561 • System Id: 2000001847 • Address: 536 MYRTLE AVENUE
Bin
3259561
System Id
2000001847
Address
536 MYRTLE AVENUE
Borough
Brooklyn
Zip Code
11205
Status
Active
Active Equip
1
Inspection Date
2021-05-19T00:00:00.000
Violation Code
AH8S
Law Section
24 RCNY §8-05(f)(3)
Violation Text
Legionella samples not collected or analyzed, or results not recorded or reported to DOHMH as required
Violation Type
PHH
Citation Text
At the time of inspection, on-site representative failed to provide report or chain of custody form that the required collection of Legionella samples were taken while the cooling tower system was in operation for entire calender year of 2020-2021.
Summons Number
0881245815
Inspection Type
Cycle
Bbl
3019057501
Latitude
40.693456
Longitude
-73.963546
Community Board
302
Council District
35
Census Tract
019300
Nta Code
BK0204
VIEW LOCATION
0881245824
Bin: 3259561 • System Id: 2000001847 • Address: 536 MYRTLE AVENUE
Bin
3259561
System Id
2000001847
Address
536 MYRTLE AVENUE
Borough
Brooklyn
Zip Code
11205
Status
Active
Active Equip
1
Inspection Date
2021-05-19T00:00:00.000
Violation Code
AH8T
Law Section
24 RCNY §8-05(f)(4)
Violation Text
Failure to monitor and sample from representative locations and times
Violation Type
Critical
Citation Text
Respondent is in violation of 24 RCNY 8-05(f)(4) in that records produced by on-site representative and reviewed by Department at the time of inspection failed to demonstrate proof of water quality monitoring and sampling locations.. Respondent is in violation of 24 RCNY 8-05(f)(4) in that operational records produced by on-site representative and reviewed by Department at the time of inspection were missing required sampling locations for samples collected on the following dates: pertinent records not provided At the time of inspection, records provided by on-site representative and reviewed by Department indicated that locations of Legionella sampling were missing. , Respondent failed to provide Legionella sampling collection times for samples collected throughout the calender year of 2020-2021. On site person Mr. Charlie informed inspectors that location has no operational records at time of inspection.
Summons Number
0881245824
Inspection Type
Cycle
Bbl
3019057501
Latitude
40.693456
Longitude
-73.963546
Community Board
302
Council District
35
Census Tract
019300
Nta Code
BK0204
VIEW LOCATION
0881245833
Bin: 3259561 • System Id: 2000001847 • Address: 536 MYRTLE AVENUE
Bin
3259561
System Id
2000001847
Address
536 MYRTLE AVENUE
Borough
Brooklyn
Zip Code
11205
Status
Active
Active Equip
1
Inspection Date
2021-05-19T00:00:00.000
Violation Code
AH8X
Law Section
24 RCNY §8-06(b)(2)
Violation Text
Legionella samples not collected, analyzed before system start-up
Violation Type
General
Citation Text
At the time of inspection, operational records provided by Respondent failed to produce sufficient evidence in the form of a lab report or chain-of-custody form that the required startup-up Legionella culture collection had been conducted during the following documented startup time period: pertinent records not provided
Summons Number
0881245833
Inspection Type
Cycle
Bbl
3019057501
Latitude
40.693456
Longitude
-73.963546
Community Board
302
Council District
35
Census Tract
019300
Nta Code
BK0204
VIEW LOCATION
3259561
Bin: 3259561 • System Id: 2000001847 • Address: 536 MYRTLE AVENUE
Bin
3259561
System Id
2000001847
Address
536 MYRTLE AVENUE
Borough
Brooklyn
Zip Code
11205
Status
Active
Active Equip
1
Inspection Date
2021-05-19T00:00:00.000
Violation Code
AH9C
Law Section
24 RCNY §8-07(c)
Violation Text
DOB Cooling Tower Registration Number not posted as required
Violation Type
General
Citation Text
Respondent is in violation of 8-07(c) in that, at the time of inspection, Inspector observed that the cooling tower system's Department of Buildings Cooling Tower registration number was not posted on the cooling tower.
Inspection Type
Cycle
Bbl
3019057501
Latitude
40.693456
Longitude
-73.963546
Community Board
302
Council District
35
Census Tract
019300
Nta Code
BK0204
VIEW LOCATION
3326830
Bin: 3326830 • System Id: 2000012212 • Address: 5100 KINGS PLAZA
Bin
3326830
System Id
2000012212
Address
5100 KINGS PLAZA
Borough
Brooklyn
Zip Code
11234
Status
Active
Active Equip
1
Inspection Date
2022-01-25T00:00:00.000
Inspection Type
Cycle
Bbl
3084700055
Latitude
40.60972
Longitude
-73.919516
Community Board
318
Council District
46
Census Tract
069800
Nta Code
BK1802
VIEW LOCATION
1023161
Bin: 1023161 • System Id: 2000013872 • Address: 1301 AVENUE OF THE AMERICAS
Bin
1023161
System Id
2000013872
Address
1301 AVENUE OF THE AMERICAS
Borough
Manhattan
Zip Code
10019
Status
Active
Active Equip
1
Inspection Date
2020-02-18T00:00:00.000
Inspection Type
Cycle
Bbl
1010050029
Latitude
40.761768
Longitude
-73.980027
Community Board
105
Council District
04
Census Tract
013100
Nta Code
MN0502
VIEW LOCATION
0881203474
Bin: 3259561 • System Id: 2000001847 • Address: 536 MYRTLE AVENUE
Bin
3259561
System Id
2000001847
Address
536 MYRTLE AVENUE
Borough
Brooklyn
Zip Code
11205
Status
Active
Active Equip
1
Inspection Date
2020-02-19T00:00:00.000
Violation Code
AH8B
Law Section
24 RCNY §8-03
Violation Text
Maintenance Program and Plan incomplete or not on premises
Violation Type
Critical
Citation Text
Respondent is in violation of 24 RCNY 8-03 in that the required Maintenance Program and Plan for the cooling tower system was not kept on premises at the date and time of inspection noted above. The on-site representative was requested to provide missing record during inspection and at final review of violation deficiencies but was not able to do so.Respondent is in violation of 24 RCNY 8-03 in that the MPP was not made available at the date and time of inspection noted above. The on-site representative was requested to provide missing record during inspection and at final review of violation deficiencies but was not able to do so.
Summons Number
0881203474
Inspection Type
Cycle
Bbl
3019057501
Latitude
40.693456
Longitude
-73.963546
Community Board
302
Council District
35
Census Tract
019300
Nta Code
BK0204
VIEW LOCATION
0881203483
Bin: 3259561 • System Id: 2000001847 • Address: 536 MYRTLE AVENUE
Bin
3259561
System Id
2000001847
Address
536 MYRTLE AVENUE
Borough
Brooklyn
Zip Code
11205
Status
Active
Active Equip
1
Inspection Date
2020-02-19T00:00:00.000
Violation Code
AH8C
Law Section
24 RCNY §8-04(a)
Violation Text
Routine monitoring not conducted, documented at least once a week when tower is in use
Violation Type
Critical
Citation Text
Respondent is in violation of 24 RCNY 8-04(a)(1) in that the operational records provided by on-site representative and reviewed by Department at the time of inspection failed to demonstrate that all weekly routine system monitoring had taken place while the cooling tower system was in operation.
Summons Number
0881203483
Inspection Type
Cycle
Bbl
3019057501
Latitude
40.693456
Longitude
-73.963546
Community Board
302
Council District
35
Census Tract
019300
Nta Code
BK0204
VIEW LOCATION